THE FRONT FACE SEAL MUST BE FLAT TO ENSURE A GOOD SEAL IS FORMED BETWEEN
THE REAR AND BASE OF THE APPLIANCE AND CHIMNEY TO AVOID ANY REDUCTION IN
THE NATURAL DRAUGHT.
ALWAYS ENSURE THE HEARTH IS LEVELED OFF TO HELP ENSURE NO NATURAL
DRAUGHT IS LOST BELOW BASE (SEE FIG 3)
A NON COMBUSTIBLE HEARTH MUST BE PROVIDED BENEATH THE APPLIANCE WITHIN
THE FIREPLACE OPENING.
A FIRE RESISTANT HEARTH MUST ALSO BE PROVIDED SYMMETRICALLY DISPOSED
ABOUT THE FIREPLACE OPENING A MINIMUM THICKNESS OF 12mm WITH THE
PERIMETER 50mm ABOVE THE FLOOR LEVEL
THE WIDTH MUST EXTEND A MINIMUM OF 150mm EITHER SIDE OF THE FIREPLACE
OPENING AND A DEPTH OF 300mm FROM THE FUEL BED
ANY COMBUSTIBLE MATERIAL MUST BE REMOVED ABOVE THE OPENING TO A HEIGHT
OF 900 mm ABOVE THE HEARTH LEVEL.
PURPOSE BUILT SUPERIMPOSED FIRE RESISTANT HEARTHS AND BACK PANELS,
SPECIFIED AS SUITABLE BY THE MANUFACTURERS MAY BE USED, OR A SUITABLE
PROPRIETARY FIRE SURROUND WITH A 1OO DEGREES C RATING.
CARE SHOULD BE TAKEN TO PREVENT ANY DAMAGE BEING CAUSED TO SURROUNDING
SOFT FURNISHINGS OR DECORATION.
MANY EMBOSSED VINYL WALL COVERINGS MAY BECOME DISCOLOURED IF PLACE TOO
CLOSE TO THE APPLIANCE
CHECK FLUE
CHECK THAT THE CHIMNEY CONFORMS TO THE REQUIRED SPECIFICATIONS AS